Create a new Boolean Tag with the tag name EscalateAlarm.

Enable the Digital Alarm limit in this new Tag with a Time Delay of ? Seconds.

Under the Tags tab of an existing or new Alarm Notification group the property “Set Tag When Alarm Active and Not Acknowledged” to a Boolean Tag with the Data Source of Value.

EscalateAlarm.AlarmStatusDigital can then be used to enable a second Alarm Notification monitoring the same alarms of the first Alarm Notification group with the Activate with Tag property in the second Alarm Notification Group.

Note: Under Configure-Options-Alarms uncheck “Update Alarm Status Immediately Without Alarm Time Delay”.

This will then enable the second alarm notification group when the alarms monitored in the first group.