Troubleshooting – Siemens

Troubleshoot Bad Data

How to identify and resolve communications errors with data sources.

  • 0:00 - Introduction
  • 0:40 - Bad Tags
  • 3:30 - System Errors
  • 4:20 - Watch Window
  • 6:20 - Error Logging
  • 7:20 - Troubleshooting Guides
  • 8:55 - Contact Us

Siemens Bad Data Quality

Below are some helpful troubleshooting steps to resolve bad data quality for tags with a Data Source of Siemens for communications to Siemens S7-200, S7-300, S7-400, S7-1200, and S7-1500 controllers.

Bad Data Quality

Processor Type

Set the Processor Type of the Driver to match the controller S7-200, S7-300, S7-400, S7-1200, or S7-1500.

Configure Drivers

Siemens Processor Type

 

Rack and CPU Slot

The Rack and CPU Slot number must be correctly set.

Configure Drivers

Siemens Rack and CPU Slot

Default Network Adapter

The Siemens driver commutates out of the default network adapter.  View Set Default Network Adapter for Driver Interfaces to see how to set the default adapter on Windows.

Siemens Controller Security

If you encounter a System Error when using the Siemens Driver Interface of Function Not Supported you may need to setup the security in the PLC to access.

View the Siemens Security Setup article for the instructions to permit access.

IP Address

When connecting to a controller the device will need to be reachable from the OAS system.  Use Windows Command Prompt or Linux terminal where the OAS Engine is running to ping the device to verify it is reachable.

ping from windows command prompt

Address

The Address field in each tag should be set to the correct memory variable that exists in the online controller.

Menu Configure Tags

Siemens Address

View Siemens Address Syntax for the correct address assignment.

If an Address is incorrectly defined to something that does not exist in the controller a System Error will be posted under Configure-System Errors listing all addresses that are invalid.

Menu Configure System Errors

Use CSV Export under Configure-Tags to open with MS Excel and to search for the tags that contain the invalid addresses that are listed.  The System Errors are also logged to text files into the OAS Error Log directory specified under Configure-Options-System Logging.

System Error 0x00000005

If the System Error 0x00000005 – Address does not exist or is out of range appears under Configure-System Errors uncheck Optimized block access attribute of dbOptimized in the controller program and re-compile and upload to the controller.

Siemens Data Type

Set the correct Siemens Data Type for the memory variable in the controller to match the data width used in the address.

Menu Configure Tags

Siemens Data Type

Data Width

Data
Width Specifier

Description

Bits

Supported
Data Types

X,
none

Bit

1

Boolean

B

Byte

8

SByte,
Byte, BCD8, String, Structured Types

W

Word

16

Int16,
UInt16, BCD16, WString

D

DWord

32

Int32,
UInt32, BCD32, Single

For Unicode character support in strings set the data type to WString with a data width of W.

Also match the OAS tag Data Type to the correct value type to be set.  If you are unsure of the data type use Object to see the result.

Tag Simple Data Types

Note: If you are using Gain and Offset in a tag to scale an integer value to a floating point value use Double Float or Single Float as the Data Type.

One or More Invalid Addresses

If one or more of the Tags defined to the Driver Interface has invalid address defined or the address does not exist in the device the remaining good addresses can be affected with either taking the device offline or invalid packet request or response.

To isolate one or more tags to their own dedicated communication channel select the existing driver interface and change the name to a new unique name and select Add Driver.

Configure Drivers

Add Driver

To define a tag to the new driver select Configure-Tags, then select the tag you want to isolate to select the new driver interface.

Menu Configure Tags

Select Driver Interface

Select Apply Changes.

Apply Changes

If the data quality changes to good for the tag then resolve the other addresses in the tags defined to the first driver interface used.

Quality Good

To help you further identify which tag addresses are bad use the Tag Watch Window to view multiple tags in one window.

To add a tag to the Watch Window,  select any tag or tag group and right click on it.  Then choose Add to Watch from the context menu.

Watch Window

The tag you selected will then appear in the Watch Window.

Watch Window

If an address is defined that does not exist in the device other tags with valid addresses can also be affected if the address is grouped into the same communication packet request as the invalid address.

 

Once you identify which addresses are invalid investigate if the address exists in the device or refer to the controller program to find the correct addresses to use.

Device Read Enabled

When the property Device Read is enabled polling communications will be disabled and read requests will only be performed when the tag defined for the Device Read transitions from false to true.  If data is to be polled continuously from the device disable the tag property Device Read.

Menu Configure Tags

Device Read Property

Enable by Tag

The Enable by Tag property is used to define a Boolean tag that will enable or disable communications for the tag.  If data is to be polled continuously from the device disable the tag property Enable by Tag.

Menu Configure Tags

Enable by Tag

License

Use Configure-License to verify that the Driver Siemens is enabled.

Menu Configure License

Driver Interface License Enabled

System Errors

Select Configure-System Errors and expand any Siemens Interface error to see the details of the error.

Menu Configure System Errors

AB System Errors

The information provided can often help you determine the cause of communication failures.

The history of all systems errors can be found in the OAS Error Log specified under Configure-Options-System Logging.

Menu Configure Options

Error Log Path

The default directory is the Log subdirectory in the OAS installation directory.  On Windows the default location is C:\Program Files\Open Automation Software\OAS\Log\.

 

Log Siemens Communications

You can enable the Log AB and Siemens Comm. transaction logging under Configure-Options-System Logging to track communications with the Siemens controllers.

Menu Configure Options

Log AB Communications

Specify the location of where the communication logs will be saved with the property Transaction Log Path further down in System Logging.

Transaction Log Path

Wireshark

Wireshark is an excellent third party tool to analyze network communications over Ethernet.

Use Apply a display filter field to filter the network traffic based on the IP address of the Modbus device you want to monitor with ip.addr == <IP address>, an example ip.addr == 192.168.0.1

You can download Wireshark from https://www.wireshark.org/download.html

Poor Network or Line Quality

If communication failures are intermittent due to faulty network you can increase the Transaction Timeout under Configure-Drivers.

Configure Drivers

Transaction Timeout

The default Timeout is 1000 milliseconds (1 second).

I get the error 33028 Error: device error (S7) 0X00008104 Function is not supported.
The error is related  to the security setting in the PLC. Follow these steps in Step 7 (TIA Portal): Siemens Security Setup