How to Transfer Data from Sparkplug B to Siemens

How to Transfer Data from Sparkplug B to Siemens

Open Automation Software can be used to transfer data from Sparkplug B Edge of Network devices to a Siemens device locally or over a network. This guide walks you through downloading and installing OAS, configuring a simulated Edge of Network node, a Host App connector, a Siemens connector and a tag to write to the Siemens device.

Typically you will also have an Edge of Network (EoN) node configured. For the purposes of this guide, you will create an EoN node and a Tag to simulate data changes. You can also use your own EoN node if you already have one.

This guide uses the Data Route feature of OAS to transfer a Tag's value to another Tag's value using the Tag-to-Tag method.

For this guide on how to transfer data between Sparkplug B and a Siemens device you will need:

  • A Siemens device connected to your workstation

1 - Download and Install OAS

If you have not already done so, you will need to download and install the OAS platform.

Fully functional trial versions of the software are available for Windows, Windows IoT Core, Linux, Raspberry Pi and Docker on our downloads page.

On Windows, run the downloaded setup.exe file to install the Open Automation Software platform. For a default installation, Agree to the End User License Agreement and then click the Next button on each of the installation steps until it has completed.

If you'd like to customize your installation or learn more, use the following instructions:

The OAS Service Control application will appear when the installation finishes on Windows.

OAS Service Control

Click on each START SERVICE button to start each of the three OAS services.

2 - Configure OAS

Configure OAS is the main application used to configure local and remote OAS instances.

OAS Logo

  1. From your operating system start menu, open the Configure OAS application.

  2. Select the Configure > Tags screen.

    Important

    If this is the first time you have installed OAS, the AdminCreate utility will run when you select a screen in the Configure menu. This will ask you to create a username and password for the admin user. This user will have full permissions in the OAS platform.

    For further information see Getting Started - Security.

  3. If this is the first time you are logging in, you will see the AdminCreate utility. Follow the prompts to set up your admin account. Otherwise, select the Log In menu button and provide the Network Node, username and password.

    Log In Menu

    Log In Dialog

Info

In this guide you will use the Configure OAS application to configure the local Network Node which by default is localhost.

If you have installed OAS on a remote instance you can also connect to the remote instance by setting the relevant IP address or host name in the Network Node field.

3 - Check that the MQTT Broker is enabled

If you are using the OAS MQTT Broker, you can follow the steps below to ensure it is enabled, otherwise you can skip this step.

  1. Select Configure > Options from the top menu.

    Configure options menu

  2. Select the MQTT Broker tab.

  3. Check that the OAS MQTT Broker Enable checkbox is checked and the OAS MQTT Broker Port is configured as 1883.

    MQTT broker options

4 - Create Security Group and User

When using Sparkplug B over the OAS MQTT Broker, you need to configure a security group and a user to provide Tag read/write access. You'll need these credentials when creating the Sparkplug B connector instances later.

ℹ️ You can skip this step if you already have your own MQTT Broker.

  1. Select Configure > Security from the top menu.

    Configure drivers menu

  2. Provide a Group Name such as SparkplugAccess.

    Sparkplug B security group name

  3. Click on the DISABLE ALL button to disable all access.

    Disable all access button

  4. In the Read Tags tab, ensure Disable All Tags From Reading is NOT checked.

    Read tags not disabled

  5. In the Write Tags tab, ensure Disable Add Tags From Writing is NOT checked.

    Write tags not disabled

  6. Click on the ADD GROUP button on the left hand side to add this security group configuration. Once added, the security group name should appear in the list of security groups.

    Add security group button

  7. Select Configure > Users from the top menu.

    Configure drivers menu

  8. Provide a User Name such as sparkpluguser, a password and set the Security Group as SparkplugAccess.

    Set username and security group

  9. Click on the ADD USER button on the left hand side to add this user configuration. Once added, the user name should appear in the list of users.

    Add user button

5 - Create Sparkplug B EoN node

In order to simulate an Edge of Network (EoN) node, we can use the features available in OAS to create an EoN using a Sparkplug B connector instance and leverage the built-in MQTT broker.

ℹ️ You can skip this section if you want to use your own existing EoN node. You'll have to ensure that your EoN node is configured with the details in step 3 below so that it can talk to the OAS Host App.

  1. Select Configure > Drivers from the top menu.

    Configure drivers menu

  2. Enter a name such as EoN Node A in the Driver Interface Name to give this driver interface a unique name.

  3. Ensure the following parameters are configured:

    • Driver: Sparkplug B
    • Host: localhost
    • Port: 1883
    • User Name: sparkpluguser
    • Password: the password you configured in the previous step
    • Protocol Driver: V500
    • Client ID: OAS_Node
    • Mode: Edge Node
    • Group ID: Group1
    • Edge Node ID: NodeA

    EoN node configuration

  4. Click on the ADD DRIVER button on the left hand side to add this driver configuration. Once added, the driver interface name should appear in the list of drivers.

    Add EoN driver button

6 - Create a Tag attached to EoN for simulation

Now that the EoN node has been created we want to be able to publish data from it so we can simulate data being generated by the EoN node. We'll need this to test the Sparkplug B Host App we will create in the next step.

ℹ️ If you skipped creating an EoN node in OAS and you already have your own EoN node configured, you can skip this section as well and instead generate some data in your own EoN node.

  1. Select Configure > Tags from the top menu.

    Configure tags menu

  2. If you want to add a Tag to the root Tags group make sure the Tags node is selected in the tag list and click on the ADD TAG button.

    Add tag button

    If you want to add a Tag to a Tag Group, select the Tag Group first and then click on the ADD TAG button.

    You can also add Tag Groups by using the ADD GROUP button.

  3. Provide a Tag Name such as TemperatureSensor and click the OK button.

    Add tag to root node dialog

  4. To assign this Tag to a Sparkplug B node configure the Host properties to match your EoN node Group ID and Edge Node ID properties.

    • Host Group ID: Group1
    • Host Edge Node ID: NodeA
    • Host Device ID: EoN Sim
    • Host Metric Name: Temperature

    Set host EoN properties

  5. Click on the Apply Changes button to apply the changes.

7 - Set up Sparkplug B Host App to receive data from the EoN node

In this section you will create a Sparkplug B driver configured using Host App mode, which will also automatically create the Tags provided by the EoN node.

  1. Select Configure > Drivers from the top menu.

    Configure drivers menu

  2. Enter a name such as SpB Host App in the Driver Interface Name to give this driver interface a unique name.

  3. Ensure the following parameters are configured:

    • Driver: Sparkplug B
    • Host: localhost
    • Port: 1883
    • User Name: sparkpluguser
    • Password: the password you configured in the previous step
    • Protocol Driver: V500
    • Client ID: OAS_Client_Host
    • Mode: Host App
    • Host ID: OAS_Host (this needs to match in the EoN node driver)

    Host App configuration

    ℹ️ If you are using your own MQTT Broker, ensure that you configure the Host, Port, User Name, Password and Protocol Driver accordingly.

  4. Click on the ADD DRIVER button on the left hand side to add this driver configuration. Once added, the driver interface name should appear in the list of drivers.

    Add Host App driver button

Tips

When the Add Client Tags Automatically option is enabled in the Sparkplug B Host App driver, OAS will automatically generate the Tags that are registered with the EoN nodes. You can see these in the next step.

8 - Verify Host App Tag Generation

You will now check to make sure the Tag Group folder structure and Tag for the Temperature metric was automatically generated and that any updates to the TemperatureSensor tag will flow through from the EoN node to the generated Tag.

  1. Select Configure > Tags from the top menu.

    Configure tags menu

    Tips

    If you were already on the Tags screen, you may need to click on the SELECT button next to the Network Node drop-down list to refresh the tag list.

  2. You will see a Tag Group structure starting with a parent folder called SpB Host App and then a sub-folder for Group1, another sub-folder for NodeA and finally a sub-folder for the EoN node called EoN Sim. The Temperature tag representing the Temperature metric is inside this final sub-folder.

    As you can see the Sparkplug B host app driver has automatically generated the folder structure and Tags.

    Generated tag group structure

  3. Select the Temperature tag in the EoN Sim sub-folder. You should see a value of zero (0) and the Client parameters configured according to the EoN node Host properties. These properties were automatically configured by OAS.

    Check temperature metric value

  4. Now you will test the data flow.

    ℹ️ If you have your own EoN node configured and you skipped creating an EoN node in OAS then you can trigger a data change in your EoN node to test the configuration.

    If you created an EoN node in OAS you can select the TemperatureSensor tag in the root Tags folder. Type in a value of 24.9 in the Enter Value field and click on the Apply Changes button. If everything is working correctly, this change should trigger the EoN node to publish a new value via the OAS MQTT Broker.

    Set temperature value

  5. Select the Temperature tag again in the EoN Sim sub-folder. You should now see a value of 24.9.

    Confirm temperature metric value change

9 - Configure Siemens Data Destination

In the following steps you will create and configure an Siemens Connector to act as a data destination. This guide assumes that you have an S7-1200 or similar series controller connected to the same network as the OAS instance.

  1. Select Configure > Drivers from the top menu.

    Configure drivers menu

  2. Enter a meaningful Driver Interface Name to give this driver interface instance a unique name.

  3. Ensure the following parameters are configured:

    • Driver: Siemens
    • IP Address: Your controller IP address
    • Processor Type: S7 1200 (or your own controller type)
    • Link Type: PC

    Siemens connector configuration

  4. Click on the ADD DRIVER button on the left hand side to add this driver configuration. Once added, the driver interface name should appear in the list of drivers.

    Add driver button

10 - Add Data Destination Tag

In this section you will create a Tag to represent a data point that you want to write to.

  1. Select Configure > Tags from the top menu.

    Configure tags menu

  2. If you want to add a Tag to the root Tags group make sure the Tags node is selected in the tag list and click on the ADD TAG button.

    Add tag button

    If you want to add a Tag to a Tag Group, select the Tag Group first and then click on the ADD TAG button.

    You can also add Tag Groups by using the ADD GROUP button.

  3. Provide a Tag Name such as TemperatureOutput and click the OK button.

    Add tag to root node dialog

11 - Assign Siemens as Tag Data Destination

You will now set the Tag's data source to the Siemens driver interface that you created previously to act as a data destination.

  1. Select the Tag that will be associated with the Siemens destination.

    Tag

  2. Set the Data Source to Siemens.

  3. Set the Select Driver Interface drop-down to the S7-1200-Destination interface created previously.

  4. In the Address field enter the address of an analog input (for example MD0). Adjust the Siemens Data Type if required.

    Siemens tag configuration

    Info

    For more information about Siemens addressing see the article Siemens Address Syntax

  5. Set the polling rate in seconds by setting the Polling Rate property [default: 1 second].

  6. Click on the Apply Changes button to apply the changes.

  7. Check that the quality status is Good Quality and the data in the Value field is as expected. If the PLC does not hold any value in the given register then the value will remain zero.

12 - Configure Tag-To-Tag Data Route

In this section you will configure the Target of the source Tag to be the destination Tag value. This means whenever the source Tag value is updated, the destination Tag value will also be updated. This will cause a write operation on any associated driver if it is supported.

  1. Select the source data Tag.

    Select temperature sensor Tag

  2. Select the Target tab.

    Select Target tab

  3. Enable the Enable Write to Target option.

    Enable Tag Target

  4. Click on the BROWSE button to select the destination tag.

    Select destination Tag

  5. Optionally, configure the Deadband property or enable Write Continuously to configure a continuous writing frequency.

    Complete Tag Target Configuration

  6. Click on the Apply Changes button to apply the configuration.

  7. To verify that your data transfer is working correctly, select the destination Tag and check that the Tag value matches the Tag value of the source Tag.

    Temperature Output Tag

    You should also verify that the Tag value has been written to your destination device. Depending on your configuration in step 5 above, this destination value should be updated whenever the source value changes or at the given frequency.

13 - Save Changes

Once you have successfully configured your OAS instances, make sure you save your configuration.

On each configuration page, click on the Save button.

If this is the first time you are saving the configuration, or if you are changing the name of the configuration file, OAS will ask you if you want to change the default configuration file.

If you select Yes then OAS will make this configuration file the default and if the OAS service is restarted then this file will be loaded on start-up.

If you select No then OAS will still save your configuration file, but it will not be the default file that is loaded on start-up.

Change Default Configuration Files dialog

Important

Each configuration screen has an independent configuration file except for the Tags and Drivers configurations, which share the same configuration file. It is still important to click on the Save button whenever you make any changes.

For more information see: Save and Load Configuration

Info

  • On Windows the configuration files are stored in C:\ProgramData\OpenAutomationSoftware\ConfigFiles.
  • On Linux the configuration files are stored in the ConfigFiles subfolder of the OAS installation path.